1MDU07212-YN Rev. D Section 6
Installation
REF601 / REJ601 / REM601 77
Application Manual
Table 31: Configuration
Configuration
Parameter
Actual
value
Default
value
Unit
Range
Resolution
Blocking: I> / 51
NO
-
NO; YES
-
Blocking: I>> / 50-1
NO
-
NO; YES
-
Blocking: I>>> / 50-2
NO
-
NO; YES
-
Blocking: Io> / 51N
NO
-
NO; YES
-
Blocking: Io>> / 50N
NO
-
NO; YES
-
Blocking: 3Ith> / 49
NO
-
NO; YES
-
Blocking: I2> / 46
NO
-
NO; YES
-
Blocking: I2/I1> / 46PD
NO
-
NO; YES
-
Blocking: BF
NO
-
NO; YES
-
Blocking: O -> I / 79
NO
-
NO; YES
-
Blocking Remote Ctrl
NO
-
NO; YES
-
Block TCS
NO
-
NO; YES
-
TCS Operate Time
5
sec
1 … 300
1
Earth type / I0 meas.
External
Internal; External
-
CT Ipn
1000
A
20 … 9999
1
CT Isn
1
A
1; 5
-
Frequency
50
Hz
50; 60
-
COM Parameters
Protocol
MODBUS RTU
IEC 60870-5-103
Comm. Baud Rate
19200
-
MODBUS: 2400; 4800; 9600;
19200; 38400
IEC_103: 9600; 19200
-
Relay Addr
001
-
MODBUS: 001 … 247
IEC_103: 001…254
-
Comm. Parity
Even
-
MODBUS: None; Odd; Even
IEC_103: None; Even
-
Class2 Intv (IEC_103)
10
sec
0…60 sec
Class2 SF
2.4
1.2; 2.4
Comm Admin Level
Yes
-
NO; YES
-