Table 15. High-speed output HSO with BIO0007
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 6 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Operate time <1 ms
Reset <20 ms, resistive load
Table 16. Front port Ethernet interfaces
Ethernet interface
Protocol Cable Data transfer rate
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
Table 17. Station communication link, fiber optic
Connector
Fiber type
1)
Wave length Typical max.
length
2)
Permitted path attenuation
3)
LC MM 62.5/125 or 50/125 μm
glass fiber core
1300 nm 2 km <8 dB
ST MM 62.5/125 or 50/125 μm
glass fiber core
820...900 nm 1 km <11 dB
1) (MM) multi-mode fiber, (SM) single-mode fiber
2) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path.
3) Maximum allowed attenuation caused by connectors and cable together
Table 18. IRIG-B
Description
Value
IRIG time code format
B004, B005
1)
Isolation 500V 1 min
Modulation Unmodulated
Logic level 5 V TTL
Current consumption <4 mA
Power consumption <20 mW
1) According to the 200-04 IRIG standard
Table 19. Lens sensor and optical fiber for arc protection
Description
Value
Fiber optic cable including lens 1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40...+100°C
Maximum service temperature range of the lens, max 1 h +140°C
Minimum permissible bending radius of the connection fiber 100 mm
Transformer Protection and Control
1MRS756891 M
RET615