EasyManua.ls Logo

ABB Relion 615 series - Page 32

ABB Relion 615 series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 20. Degree of protection of flush-mounted protection relay
Description Value
Front side IP 54
Rear side, connection terminals IP 20
Table 21. Environmental conditions
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range
-40...+85ºC (<16h)
1)2)
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 2000 m
Transport and storage temperature range -40...+85ºC
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For relays with an LC communication interface the maximum operating temperature is +70 ºC
Transformer Protection and Control
1MRS756891 M
RET615
Product version: 5.0 FP1
32 ABB