1MAC308145-MB E Section 3
RER620 application
RER620 47
Application Manual
Figure 29: Synch-check function
RER620 “Latched Open” logic scheme:
The RER620 has a user settable “Latched Open” logic scheme as a part of default
configuration. This logic scheme will use one local HMI push button which will
immediately open all breaker poles (see Figure 9 and Figure 27) and set the
SECRSYN1(25;SYN
BLOCK
CL_COMMAND
BYPASS
SYNC_INPRO
SYNC_OK
CL_FAIL_AL
CMD_FAIL_AL
LLDB
LLLB
DLLB
DLDB
AND
B1
B2
O
NOT
IN OUT
OR
B1
B2
O
SEQRFUF1_60_FUSEF_U
SECRSYN1_25_SYNC_OK
SPCGGIO2_25_BLK
SPCGGIO2_25_BLK
SECRSYN1_25_SYNC_INPRO
Note:
In synch-check function the two voltage inputs
are referred to as Bus and Line while RER620
the inputs are referred to as Source-1 and
Source-2.
Unless otherwise indicated, consider
Source-1 as Bus and Source-2 as Line side.
For example if Source 2 voltage goes below
the ‘dead’ threshold setting, the same will be
considered as Line Dead as TRUE by synchro
check function. If Source 2 voltage goes
above ‘live’ threshold, the Live Line will be
TRUE.