EasyManua.ls Logo

ABB Relion 620 Series - Page 19

ABB Relion 620 Series
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Lift the handle to 90 degrees to release the latching mechanism.
The plug-in unit is pushed about 7 mm out of the case and the connectors are
separated.
4. Pull the unit out of the case.
Figure 2: Detaching a plug-in unit from the case
The protection relay features an automatic short-circuit mechanism in
the CT connector. Therefore, detaching the plug-in unit will not open the
secondary circuit of the CT which could cause dangerously high voltages.
Do not touch terminals inside the case after removing the plug-in unit.
Live terminals can be inside the case.
The signal connectors are left open when the plug-in unit is detached.