5.4.3 Connecting RTD and mA inputs
Connect the wires from the transducers to the correct device according to the
connection diagram.
Each terminal for RTDs and mA inputs is dimensioned for one 0.5...2.5 mm
2
wire
or for two 0.5...1.0 mm
2
wires.
See the specific card variant from the application manual.
Connect the RTD earth cable shield to the protective earth.
X130
3
4
5
6
7
8
RTD 1
RTD 2
mA 1
mA
1
2
RTD 1 GND
RTD 2 GND
10
9
11
13
12
14
16
17
SO2
SO1
SO3
RTD0002
Figure 41: Example of RTD0002 card variant, (2 RTD + 1 mA + 3 SO + TCS)
Connecting
1MRS757641 G
52 620 series
Installation Manual