Binary input/
output modules
Ordering no #10 Notes and rules
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1 BIM required in position P3 and 1 BOM required in position P4.
IOM 8 inputs, RL
220-250 VDC,
50mA, 10+2
output relays
1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
IOM 8 inputs, RL
220-250 VDC,
110mA, 10+2
output relays
1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
IOM with MOV 8
inputs, RL 24-30
VDC, 50mA,
10+2 output
relays
1MRK000173-GC U U U U U U U U U U U U
IOM with MOV 8
inputs, RL 48-60
VDC, 50mA,
10+2 output
relays
1MRK000173-AD V V V V V V V V V V V V
IOM with MOV 8
inputs, RL
110-125 VDC,
50mA, 10+2
output relays
1MRK000173-BD W W W W W W W W W W W W
IOM with MOV 8
inputs, RL
220-250 VDC,
50mA, 10+2
output relays
1MRK000173-CD Y Y Y Y Y Y Y Y Y Y Y Y
mA input
module MIM 6
channels
1MRK000284-AB R R R R R R R R R R R R
3)
SOM static
output module,
6 heavy duty
static outputs,
250 VDC + 6
output relays
1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2
4)
Selection for
position #10
C
1) These black marks indicate the maximum number of modules per casing type and the slots that can be occupied.
2) Maximum 4 (BOM+SOM+MIM) boards.
3) maximum 1 MIM board in 1/2 case
4) SOM must not to be placed in position nearest to NUM: 1/2 case slot P5, 3/4 case 1 TRM slot P10, 3/4 case 2 TRM slot P7, 1/1 case 2 TRM slot P13, 1/1 case, 1 TRM slot P16.
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2