Section 8 Editing the network settings
GUID-46742F3A-48A3-4C24-A354-AD721C69023C v1
Before starting the PCM600 program, edit the network settings of the computer system. The
computer system and the IED should be configured to communicate correctly because both will be
available on the same network. This is possible when the IED and the computer system have the
same Subnet Mask but different IP addresses.
Figure shows this concept and the addresses are used as an example; other addresses can also be
used.
Subnet Mask for both:
255.255.255.0
IEC18000032-1-en.vsdx
670 IED
IP address (Front Port): 10.1.150.3
PC
IP address: 10.1.150.4
IEC18000032 V1 EN-US
Figure 15: Network settings to connect PC with an IED
Based on the version of the Windows operating system, follow the instructions to edit network
settings.
The PCM600 software version 2.8 or later is used to connect to the IED that
supports Windows XP, 7, 8, 8.1, and 10.
8.1 Setting up communication between PCM600 and the IED
SEMOD58570-5 v15
The communication between the IED and PCM600 is independent of the communication protocol
used within the substation or to the NCC.
1MRK 500 129-UUS B Section 8
Editing the network settings
670/650 series 35
Quick start guide