Access rights VIEWER OPERATOR ENGINEER INSTALLER SECADM SECAUD RBACMNT ADMINISTRATOR
Control – Basic - X X - - - - -
Control –
Advanced
- X X - - - -
-
IEDCmd – Basic - X X - - - - -
IEDCmd –
Advanced
- - X - - - -
-
FileTransfer –
Limited
- X X X X X X
X
DB Access
normal
- X X X X X X
X
Audit log read - - - - - X - X
Setting – Change
Setting Group
- X X X - - -
-
Security
Advanced
- - - - - X -
X
Table 6: Access rights explanation
Access rights Explanation
Config – Basic Configuration – Basic is intended for engineers that only adapt an existing configuration e.g. the
I/O-Configuration using SMT
Config – Advanced Configuration – Advanced is intended for engineers that do the whole application engineering
and using e.g. ACT
FileTransfer – Tools FileTransfer – Tools is used for some configuration files for the configuration and shall have the
same value as Config – Advanced
UserAdministration UserAdministration is used to handle user management e.g. adding new user
Setting – Basic Setting – Basic is used for basic settings e.g. control settings and limit supervision
Setting – Advanced Setting – Advanced is used for the relay engineer to set settings e.g. for the protection functions
Control – Basic Control – Basic is used for a normal operator without possibility to bypass safety functions e.g.
interlock or synchro-check bypass
Control – Advanced Control – Advanced is used for an operator that is trusted to do process commands that can be
dangerous
IEDCmd – Basic IEDCmd – Basic is used for commands to the IED that are not critical e.g. Clear LEDs, manual
triggering of disturbances
IEDCmd – Advanced IEDCmd – Advanced is used for commands to the IED that can hide information e.g. Clear
disturbance record
FileTransfer – Limited FileTransfer - Limited is used for access to disturbance files e.g. through FTP
DB Access normal Database access for normal user. This is needed for all users that access data from PCM
Audit log read Audit log read allows reading the audit log from the IED
Setting – Change Setting Group Setting – Change Setting Group is separated to be able to include the possibility to change the
setting group without changing any other setting
Security Advanced Security Advanced is the privilege required to do some of the more advanced security-related
settings
IED users can be created, deleted and edited only with the IED Users tool within
PCM600. From the LHMI, no users can be created nor changed.
Section 4 1MRK 511 399-UEN B
Local user account management
24 670 series 2.2 IEC
Cyber security deployment guideline