IEC15000280 V1 EN-US
Figure 22: Export SCD file
Generate the SCD file from PCM600
2. In SDM600, import SCD via the Load Structure tool. Refer to Setting Up the
SDM600 Structure in the SDM600 User Manual.
3. Update "Alternative IP Addresses" with all configured interfaces on the
device.
4. Generate certificates in the Central Account Management server for all IEDs
5. Export the certificate or the configuration package from the Central Account
Management server.
6. Use PCM600 to load the certificate and configuration into the correct IED
IED deploys only certificates bundled in a PCKS#12 file format.
1MRK 511 399-UEN B Section 5
Central Account Management
670 series 2.2 IEC 43
Cyber security deployment guideline