Off
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
7.2.3
MinRepIntVal
(1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input channel. This can be
set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic
communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an optimized way to
minimize the load on the station bus.
7.3 Logical signal status report BINSTATREP
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
7.3.1 Identification
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report BINSTATREP - -
7.3.2 Functionality
GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3
The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to
poll signals from various other functions.
7.3.3 Function block
GUID-BA0A5BC3-493B-4FE3-B4A9-14F60A88A22F v2
BINSTATREP
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
IEC09000730-1-en.vsd
IEC09000730 V1 EN-US
Figure 7: BINSTATREP function block
Section 7 1MRK 511 396-UEN E
SPA functions
30 SPA, 670 series
Communication protocol manual
© Copyright 2017 ABB. All rights reserved