7.3.5 Settings
PID-4144-SETTINGS v6
Table 13: BINSTATREP Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.0 - 60.0 s 0.1 10.0 Time delay of function
7.3.6 Operation principle
GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3
The Logical signal status report (BINSTATREP) function has 16 inputs and 16 outputs. The
output status follows the inputs and can be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
t t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 8: BINSTATREP logical diagram
Section 7 1MRK 511 396-UEN E
SPA functions
32 SPA, 670 series
Communication protocol manual
© Copyright 2017 ABB. All rights reserved