IEC 61850 name AFL-Common SA name Description DPI value FUN INF InUse ASDU GI Coding
LD0.PHPTUV1.Op.general PHPTUV1.OPERATE Operate[.general] 10=Operate general 41 90 1 2 0 1
Positive sequence undervoltage protection (1 stage)
LD0.PSPTUV1.Str.phsA - Start[.phsA] 10=PhsA start 42 64 0 2 1 1
LD0.PSPTUV1.Str.phsB - Start[.phsB] 10=PhsB start 42 65 0 2 1 1
LD0.PSPTUV1.Str.phsC - Start[.phsC] 10=PhsB start 42 66 0 2 1 1
LD0.PSPTUV1.Str.general PSPTUV1.START Start[.general] 10=Start general 42 84 1 2 1 1
LD0.PSPTUV1.Op.general PSPTUV1.OPERATE Operate[.general] 10=Operate general 42 90 1 2 0 1
Negative sequence overvoltage protection (1 stage)
LD0.NSPTOV1.Str.phsA - Start[.phsA] 10=PhsA start 43 64 0 2 1 1
LD0.NSPTOV1.Str.phsB - Start[.phsB] 10=PhsB start 43 65 0 2 1 1
LD0.NSPTOV1.Str.phsC - Start[.phsC] 10=PhsB start 43 66 0 2 1 1
LD0.NSPTOV1.Str.general NSPTOV1.START Start[.general] 10=Start general 43 84 1 2 1 1
LD0.NSPTOV1.Op.general NSPTOV1.OPERATE Operate[.general] 10=Operate general 43 90 1 2 0 1
Physical binary I/O signals
LD0.XGGIO120.Ind1.stVal - X120-Input 1 10=ON, 01=OFF 51 1 0 1 1 1
LD0.XGGIO120.Ind2.stVal - X120-Input 2 10=ON, 01=OFF 51 2 0 1 1 1
LD0.XGGIO120.Ind3.stVal - X120-Input 3 10=ON, 01=OFF 51 3 0 1 1 1
LD0.XGGIO120.Ind4.stVal - X120-Input 4 10=ON, 01=OFF 51 4 0 1 1 1
LD0.XGGIO110.Ind1.stVal - X110-Input 1 10=ON, 01=OFF 52 1 0 1 1 1
LD0.XGGIO110.Ind2.stVal - X110-Input 2 10=ON, 01=OFF 52 2 0 1 1 1
LD0.XGGIO110.Ind3.stVal - X110-Input 3 10=ON, 01=OFF 52 3 0 1 1 1
LD0.XGGIO110.Ind4.stVal - X110-Input 4 10=ON, 01=OFF 52 4 0 1 1 1
LD0.XGGIO110.Ind5.stVal - X110-Input 5 10=ON, 01=OFF 52 5 0 1 1 1
LD0.XGGIO110.Ind6.stVal - X110-Input 6 10=ON, 01=OFF 52 6 0 1 1 1
LD0.XGGIO110.Ind7.stVal - X110-Input 7 10=ON, 01=OFF 52 7 0 1 1 1
LD0.XGGIO110.Ind8.stVal - X110-Input 8 10=ON, 01=OFF 52 8 0 1 1 1
LD0.XGGIO110.SPCSO1.stVal - X110-Output 1 10=ON, 01=OFF 52 101 0 1 1 1
LD0.XGGIO110.SPCSO2.stVal - X110-Output 2 10=ON, 01=OFF 52 102 0 1 1 1
LD0.XGGIO110.SPCSO3.stVal - X110-Output 3 10=ON, 01=OFF 52 103 0 1 1 1
LD0.XGGIO110.SPCSO4.stVal - X110-Output 4 10=ON, 01=OFF 52 104 0 1 1 1
LD0.XGGIO100.SPCSO1.stVal - X100-Output 1 10=ON, 01=OFF 53 101 0 1 1 1
LD0.XGGIO100.SPCSO2.stVal - X100-Output 2 10=ON, 01=OFF 53 102 0 1 1 1
LD0.XGGIO100.SPCSO3.stVal - X100-Output 3 10=ON, 01=OFF 53 103 0 1 1 1
LD0.XGGIO100.SPCSO4.stVal - X100-Output 4 10=ON, 01=OFF 53 104 0 1 1 1
LD0.XGGIO100.SPCSO5.stVal - X100-Output 5 10=ON, 01=OFF 53 105 0 1 1 1
LD0.XGGIO100.SPCSO6.stVal - X100-Output 6 10=ON, 01=OFF 53 106 0 1 1 1
LD0.XAGGIO130.Ind1.stVal - XA130-Input 1 10=ON, 01=OFF 54 1 0 1 1 1
LD0.XAGGIO130.Ind2.stVal - XA130-Input 2 10=ON, 01=OFF 54 2 0 1 1 1
LD0.XAGGIO130.Ind3.stVal - XA130-Input 3 10=ON, 01=OFF 54 3 0 1 1 1
Table continues on next page
Section 2 1MRS756882 B
IEC 60870-5-103 data mappings
14 REM615
Point List Manual