IEC 61850 name AFL-Common SA name Description DPI value FUN INF InUse ASDU GI Coding
LD0.XAGGIO130.Ind4.stVal - XA130-Input 4 10=ON, 01=OFF 54 4 0 1 1 1
Generic operation time supervision
LD0.MDSOPT1.OpTmWrn.stVal MDSOPT1.WARNING Accum. operation time Warning 10=Warning 71 1 1 1 1 1
LD0.MDSOPT1.OpTmAlm.stVal MDSOPT1.ALARM Accum. operation time Alarm 10=Alarm 71 2 1 1 1 1
Negative sequence overcurrent protection for motors (2 stages)
LD0.MNSPTOC1.Str.general MNSPTOC1.START Stage1 start 10=Stage1 start 72 84 1 2 1 1
LD0.MNSPTOC1.Op.general MNSPTOC1.OPERATE Stage1 operate 10=Stage1 operate 72 90 1 2 0 1
LD0.MNSPTOC2.Str.general MNSPTOC2.START Stage2 start 10=Stage2 start 72 94 1 2 1 1
LD0.MNSPTOC2.Op.general MNSPTOC2.OPERATE Stage2 operate 10=Stage2 operate 72 91 1 2 0 1
Stalled motor protection
LD0.JAMPTOC1.Op.general JAMPTOC1.OPERATE Operate[.general] 10=Stage operate 73 90 1 2 0 1
Motor startup supervision
LD0.STTPMSS1.Str.general STTPMSU.MOT_START Motor startup in progress 10=Startup 74 84 1 2 1 1
LD0.STTPMSS1.Op.general STTPMSU.OPR_IIT Thermal stress operate 10=Operate 74 90 1 2 0 1
LD0.STTPRMI1.Op.general STTPMSU.OPR_STALL Stalling operate 10=Operate 74 91 1 2 0 1
Phase reversal protection
LD0.PREVPTOC1.Str.general PREVPTEOC1.START Stage start 10=Stage start 75 84 1 2 1 1
LD0.PREVPTOO1.Op.general PREVPTEOC1.OPERATE Stage operate 10=Stage operate 75 90 1 2 0 1
Motor thermal overload protection
LD0.MPPTR1.StrInh.general MPTTR1.BLK_RESTART Block restart 10=Block restart 76 83 1 2 1 1
LD0.MPPTR1.AlmThm.general MPTTR1.ALARM Thermal alarm 10=Alarm 76 85 1 2 1 1
LD0.MPPTR1.Op.general MPTTR1.OPERATE Thermal operate 10=Operate 76 90 1 2 0 1
Emegency start enabled
LD0.EMSGAPC1.Str.general
ESMGAPC1.ST_EMERG_E
NA Emergency start 10=Emergency start 77 84 1 2 1 1
Loss of load protection
LD0.LOFLPTUC1.Str.general LOFLPTUC1.START Stage1 start 10=Stage1 start 78 84 1 2 1 1
LD0.LOFLPTUC1.Op.general LOFLPTUC1.OPERATE Stage1 operate 10=Stage1 operate 78 90 1 2 0 1
ARC protection
LD0.ARCSARC11.FADet.stVal ARCSARC1.ARC_FLT_DET Stage1 Fault arc detected 10=Stage1 arc detected 156 211 1 1 0 1
LD0.ARCPTRC11.Op.general ARCSARC1.OPERATE Stage1 Operate 10=Stage1 operate 156 213 1 2 0 1
LD0.ARCSARC21.FADet.stVal ARCSARC2.ARC_FLT_DET Stage2 Fault arc detected 10=Stage2 arc detected 156 221 1 1 0 1
LD0.ARCPTRC21.Op.general ARCSARC2.OPERATE Stage2 Operate 10=Stage2 operate 156 223 1 2 0 1
LD0.ARCSARC31.FADet.stVal ARCSARC3.ARC_FLT_DET Stage3 Fault arc detected 10=Stage3 arc detected 156 231 1 1 0 1
LD0.ARCPTRC31.Op.general ARCSARC3.OPERATE Stage3 Operate 10=Stage3 operate 156 233 1 2 0 1
Non-directional earthfault protection, 2 stages (ME01 only)
LD0.EFLPTOC1.Str.general EFLPTOC1.START Low(1) stage Start 10=Low(1) stage start 159 84 1 2 1 1
LD0.EFLPTOC1.Op.general EFLPTOC1.OPERATE Low(1) stage Operate 10=Low(1) stage operate 159 90 1 2 0 1
LD0.EFHPTOC1.Str.general EFHPTOC1.START High stage start 10=High Stage start 159 96 1 2 1 1
LD0.EFHPTOC1.Op.general EFHPTOC1.OPERATE High stage operate 10=High Stage operate 159 98 1 2 0 1
Table continues on next page
1MRS756882 B Section 2
IEC 60870-5-103 data mappings
REM615 15