54
1MRS750915-MUM
Machine Terminal
Technical Reference Manual, General
REM 54_
The high-speed power outputs PS1_4_HSPO1... PS1_4_HSPO5 can also be
connected as single-pole power outputs where the object to be controlled (e.g. a
circuit breaker) is electrically connected in series with the two relay contacts, see the
figure below.
doubpole_b
Fig. 5.1.8.1.-2 High-speed single-pole power outputs (HSPO)
5.1.8.2. Single-pole power outputs (PO)
The single-pole power outputs BIO2_7_PO1 and BIO2_7_PO2 are outputs where
the object to be controlled is connected in series with two heavy-duty output relay
contacts, see the figure below. These outputs can be used for tripping purposes and
for circuit breaker and disconnector control.
PO1conn_b
Fig. 5.1.8.2.-1 Single-pole power outputs (PO)
Double-pole power outputs (PO)
The double-pole power outputs BIO2_7_PO3... BIO2_7_PO6 are outputs where the
object to be controlled (e.g. a circuit breaker) is electrically connected between the
two relay contacts, see the figure below. These outputs can be used for tripping
purposes and for circuit breaker and disconnector control.
+
-
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5
+
-
CB
e.g.
BIO2_7_PO1,