EasyManua.ls Logo

ABB REM 543 - Single-Pole Power Outputs (PO); Double-Pole Power Outputs (PO)

ABB REM 543
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
1MRS750915-MUM
Machine Terminal
Technical Reference Manual, General
REM 54_
The high-speed power outputs PS1_4_HSPO1... PS1_4_HSPO5 can also be
connected as single-pole power outputs where the object to be controlled (e.g. a
circuit breaker) is electrically connected in series with the two relay contacts, see the
figure below.
doubpole_b
Fig. 5.1.8.1.-2 High-speed single-pole power outputs (HSPO)
5.1.8.2. Single-pole power outputs (PO)
The single-pole power outputs BIO2_7_PO1 and BIO2_7_PO2 are outputs where
the object to be controlled is connected in series with two heavy-duty output relay
contacts, see the figure below. These outputs can be used for tripping purposes and
for circuit breaker and disconnector control.
PO1conn_b
Fig. 5.1.8.2.-1 Single-pole power outputs (PO)
Double-pole power outputs (PO)
The double-pole power outputs BIO2_7_PO3... BIO2_7_PO6 are outputs where the
object to be controlled (e.g. a circuit breaker) is electrically connected between the
two relay contacts, see the figure below. These outputs can be used for tripping
purposes and for circuit breaker and disconnector control.
+
-
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5
+
-
CB
e.g.
BIO2_7_PO1,
BIO2_7_PO2

Table of Contents