EasyManua.ls Logo

ABB REM 543 - Signal Outputs (SO)

ABB REM 543
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MRS750915-MUM
REM 54_
55
Machine Terminal
Technical Reference Manual, General
PO3conn_b
Fig. 5.1.8.2.-2 Double-pole power outputs (PO)
If the power outputs BIO2_7_PO3... BIO2_7_PO6 are used as single-pole outputs,
the object to be controlled is electrically connected in series with the two relay
contacts to provide sufficient breaking capacity, see the following figure.
PO2conn_b
Fig. 5.1.8.2.-3 Single-pole power outputs (PO)
Signal outputs (SO)
The signalling relay outputs (BIO1_5_SO_) are not heavy-duty outputs and thus
they cannot be used for controlling for example a circuit breaker. Available relay
contacts are either Normally Open or Normally Open/Normally Closed type (NO or
NO/NC), see the following figure. These outputs can be used for alarming and other
signalling purposes.
nonc_b
Fig. 5.1.8.2.-4 Signal outputs (SO)
+
-
CB
e.g.
BIO2_7_PO3...
BIO2_7_PO6
+
-
CB
e.g.
BIO2_7_PO3...
BIO2_7_PO6
NO/NC
NO
e.g.
PS1_4_SO1
e.g.
BIO1_5_SO1