1MRS750915-MUM
REM 54_
83
Machine Terminal
Technical Reference Manual, General
Table 5.2.1-9 Standard tests
Insulation tests Dielectric test
IEC 60255-5
Test voltage 2 kV, 50 Hz, 1 min.
Impulse voltage test
IEC 60255-5
Test voltage 5 kV, unipolar impulses,
waveform 1,2/50 µs,
source energy 0.5 J
Insulation resistance
measurements
IEC 60255-5
Insulation
resistance
> 100 MΩ, 500 V DC
Mechanical tests Vibration tests (sinusoidal) IEC 60255-21-1, class I
Shock and bump test IEC 60255-21-2, class I
Seismic tests IEC 60255-21-3, class 2
Table 5.2.1-10 Electromagnetic compatibility tests
The EMC immunity test level fulfills the requirements listed below
1 MHz burst disturbance test,
class III, IEC 60255-22-1
common mode 2.5 kV
differential mode 1.0 kV
Electrostatic discharge test,
class III
IEC 61000-4-2 and 60255-22-2
for contact discharge 6 kV
for air discharge 8 kV
Radio frequency interference
test
conducted, common mode
IEC 61000-4-6
10 V (rms), f = 150 kHz…80 MHz
radiated, amplitude-modulated
IEC 61000-4-3
10 V/m (rms),
f = 80…1000 MHz
radiated, pulse-modulated
ENV 50204
10 V/m, f = 900 MHz
radiated, test with a portable
transmitter
IEC 60255-22-3, method C
f = 77.2 MHz, P = 6 W;
f = 172.25 MHz, P = 5 W
Fast transient disturbance test
IEC 60255-22-4 and
IEC 61000-4-4
power supply 4 kV
I/O ports 2 kV
Surge immunity test
IEC 61000-4-5
power supply 4 kV, common mode
2 kV, differential mode
I/O ports 2 kV, common mode
1 kV, differential mode
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
100 A/m
Voltage dips and
short interruptions
IEC 61000-4-11
30%, 10 ms
60%, 100 ms
60%, 1000 ms
>90%, 5000 ms
Electromagnetic emission tests
EN 55011 and EN 50081-2
conducted RF emission (mains
terminal)
EN 55011, class A
radiated RF emission EN 55011, class A
CE approval Complies with the EMC directive
89/336/EEC and
the LV directive 73/23/EEC