GUID-B1E6FA9E-194A-4290-A25E-C2E49BE6BE8A V1 EN
Figure 92: Selecting the IED to be migrated
2. Select the target version in the dialog box and click Continue.
The Configuration Migration Details dialog box is displayed giving the
summary of the migration process.
3. Click Next to start the migration process.
The functions that cannot be not found in any of the lists have the same source
and the target versions and do not need to be reengineered.
The migration takes a few minutes. The PCM600 output window contains
valuable information from different parts of the migration, such as successfully
imported parameter details and the location of the newly created template. The
migration process also creates a report.
4. Wait until the migration process is completed.
5. Select the Show IED Configuration Migration Report check box to view,
print or save the report and click Finish.
The report is useful later when updating the configuration.
1MRS757810 C Section 8
Configuration migration
REC615 and RER615 129
Engineering Manual