GUID-1EC590D1-2587-441C-8A1F-2934C10BB823 V1 EN
Figure 8: Naming the data set
A maximum of 80 data attributes can be added to IED's GOOSE data sets.
Recommendation is to divide attribute amount to 20 per GOOSE data set, for
maximum performance in sender/receiver. After creating the GOOSE data sets,
define the data set entries (data attributes or data objects) for the data sets.
After creating the GOOSE data sets, define the data set entries (data attributes or data
objects) for the data sets.
If quality data attributes are added to a data set, they must be located
after the status value of the corresponding data object.
The received GOOSE data set can contain signals on the data attribute or data object
level. Data object level GOOSE entries can only be received of the following CDC
types: SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and ENS. Other CDC types
can be connected to application only when dataset is defined in attribute level.
Defining GOOSE data set entries with the IEC 61850 Configuration tool
1. Select the Data Sets tab.
2. Right-click a data set and select Details to add data attributes.