Figure 9: Opening Details
3. In the Data Set Entry window, select the data attribute or data object present in
the data set.
• Click Append selected to add the data to the end of the data set. To add a
data object level entry, select it from the FC section. To add a data attribute
level entry, select it from the DA section
• Click Insert selected to add the data above the selected row in the data set
entries list.
• To remove a data from the data set, select the data in the data set entries
pane and click Remove selected.
A maximum of 80 data attributes can be added total to IED's GOOSE data sets.
Recommendation is to divide attribute amount to 20 per GOOSE data se, for
maximum performance in sender/receiver.
If a data set has quality attributes, the attributes must be located after
the status value of the same data object.
The data attribute entries are single data, such as stVal and q. Data set
entries can be also defined on the data object level. Data object level
GOOSE entries can only be received of the following CDC types:
SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and ENS. Product
versions prior to Ver.2.0 do not support the data object level GOOSE
entries. This limitation must be considered when configuring the
whole system consisting of different product versions.
After defining the data entries for the data sets, configure the GOOSE control block
properties.