EasyManua.ls Logo

ABB RET630 - Electromagnetic Compatibility Tests

ABB RET630
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 21. Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18
IEC 60255-22-1, level 3
Common mode 2.5 kV
Differential mode 1.0 kV
Electrostatic discharge test IEC 61000-4-2
IEC 60255-22-2, level 4
IEEE C37.90.3
Contact discharge 8 kV
Air discharge 15 kV
Radio frequency interference
tests
Conducted, common mode
OK
10 V (emf), f=150 kHz...80
MHz
IEC 61000-4-6
IEC 60255-22-6, level 3
Radiated, pulse-modulated 10 V/m, f=900 MHz ENV 50204
IEC 60255-22-3
Radiated, amplitude-
modulated
20 V/m (rms), f=80...1000
MHz
IEEE C37.90.2-2004
10 V/m, f=80...2700 MHz IEC 61000-4-3
IEC 60255-22-3
Fast transient disturbance
tests
IEC 61000-4-4
IEC 60255-22-4, class A
Communication ports 2 kV
Other ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-22-5, level 4/3
Binary inputs 2 kV line-to-earth, 1kV line-to-
line
Communication 1 kV line-to-earth
Other ports 4 kV line-to-earth, 2 kV line-
to-line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8, level 5
Transformer Protection and Control 1MRS756788 A
RET630
Product version: 1.0 Issued: 15.09.2009
20 ABB

Table of Contents

Related product manuals