ABB RET630 - Directional Earth-Fault Protection Main Settings

ABB RET630
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 34. Directional earth-fault protection (DEFxPDEF) main settings
Parameter Function Value (Range) Step
Start Value DEFLPDEF 0.010...5.000 pu 0.005
DEFHPDEF 0.10...40.00 pu 0.01
Directional mode DEFLPDEF and
DEFHPDEF
1=Non-directional
2=Forward
3=Reverse
Time multiplier DEFLPDEF 0.05...15.00 0.05
DEFHPDEF 0.05...15.00 0.05
Operate delay time DEFLPDEF 0.06...200.00 s 0.01
DEFHPDEF 0.06...200.00 s 0.01
Operating curve
type
1)
DEFLPDEF Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
13, 14, 15, 17, 18, 19
DEFHPDEF Definite or inverse time
Curve type: 1, 3, 5, 15, 17
Operation mode DEFLPDEF and
DEFHPDEF
1=Phase angle
2=I
0
Sin
3=I
0
Cos
4=Phase angle 80
5=Phase angle 88
1) For further reference please refer to the Operating characteristics table
Transformer Protection and Control 1MRS756788 A
RET630
Product version: 1.0 Issued: 15.09.2009
ABB 31