ABB RET630 - Control Functions; Operation Characteristics; Synchrocheck (SYNCRSYN)

ABB RET630
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 67. Operation characteristics
Parameter Values (Range)
Operating curve type 1=ANSI Ext. inv.
2=ANSI Very. inv.
3=ANSI Norm. inv.
4=ANSI Mod inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Operating curve type (voltage protection)
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
Control functions
Table 68. Synchrocheck (SYNCRSYN)
Characteristic Value
Operation accuracy At the frequency f = f
n
Voltage: ±1.0% or ±0.002 x U
n
Frequency: ±10 mHz
Phase angle ±2°
Reset time < 50 ms
Reset ratio Typical 0.96
Operate time accuracy ±1.0% of the set value or ±20 ms
Transformer Protection and Control 1MRS756788 A
RET630
Product version: 1.0 Issued: 15.09.2009
46 ABB