The preconfiguration determines the I/O hardware and hardware variants. Choose the digits from
one of the blue preconfiguration rows below to define the correct digits for # 4-8. The example be-
low shows preconfiguration “B” with chosen options.
S B T B A B A C B B B Z A A N A X A
# DESCRIPTION
4-8
Functional application, preconfigurations:
A = Preconfiguration A for two-winding transformers
B = Preconfiguration B for two-winding transformers,
including numerical REF protection
N = None
Pre-
conf.
# 4
Available analog
inputs options
# 5-6
Available binary in-
puts/output options
# 7-8
A
AA = 7 I (I
0
1/5A) + 3U
AB = 23 BI + 18 BO
or
AC = 32 BI + 27 BO
B
AB = 8 I (I
0
1/5A) + 2U
AB = 23 BI + 18 BO
or
AC = 32 BI + 27 BO
N
AA = 7 I (I
0
1/5A) + 3U
or
AB = 8 I (I
0
1/5A) + 2U
or
AC = 7 I (I
0
1/5A) +
1 I (I
0
0.1/0.5A) + 2U
AA = 14 BI + 9 BO
or
AB = 23 BI + 18 BO
or
AC = 32 BI + 27 BO
GUID-2BC2543E-A96E-4F79-9685-772DF5C80474 V1 EN
S B T B A B A C B B B Z A A N A X A
# DESCRIPTION
9
Communication serial
1)
Glass fibre (ST connector)
A
Plastic fibre (snap-in connector)
B
10 Communication Ethernet
Ethernet 100BaseFX (LC)
A
Ethernet 100BaseTX (RJ-45)
B
11 Communication protocol
IEC 61850
A
IEC 61850 and DNP3 TCP/IP
B
1)
For future use
GUID-F13B8117-3239-4EBE-A7CC-FF44E6D56764 V1 EN