EasyManua.ls Logo

ABB REV615 - Multipurpose Protection (MAPGAPC); Arc Protection (ARCSARC)

ABB REV615
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 51. Arc protection (ARCSARC)
Characteristic Value
Operation accuracy ±3% of the set value or ±0.01 × I
n
Operate time Minimum Typical Maximum
Operation mode
= "Light
+current"
1)2)
9 ms
3)
4 ms
4)
12 ms
3)
6 ms
4)
15 ms
3)
9 ms
4)
Operation mode
= "Light only"
2)
9 ms
3)
4 ms
4)
10 ms
3)
6 ms
4)
12 ms
3)
7 ms
4)
Reset time Typically 40 ms
Reset ratio Typically 0.96
1)
Phase start value
= 1.0 × I
n
, current before fault = 2.0 × set
Phase start value
, f
n
= 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the heavy-duty output contact
3) Normal power output
4) High-speed output
Table 52. Arc protection (ARCSARC) main settings
Parameter
Function Value (Range) Step
Phase start value ARCSARC 0.50...40.00 × I
n
0.01
Ground start value ARCSARC 0.05...8.00 × I
n
0.01
Operation mode ARCSARC 2 = Light only
3 = BI controlled
-
Table 53. Multipurpose protection (MAPGAPC)
Characteristic
Value
Operation accuracy ±1.0% of the set value or ±20 ms
Table 54. Multipurpose protection (MAPGAPC) main settings
Parameter
Function Value (Range) Step
Start value MAPGAPC -10000.0...10000.0 0.1
Operate delay time MAPGAPC 0...200000 ms 100
Operation mode MAPGAPC 1 = Over
2 = Under
-
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
36 ABB

Table of Contents

Related product manuals