Table 58. Current unbalance protection for shunt capacitor banks (CUBPTOC) main settings
Parameter Function Value (Range) Step
Alarm mode CUBPTOC 1 = Normal
2 = Element counter
-
Start value CUBPTOC 0.01...1.00 × I
n
0.01
Alarm start value CUBPTOC 0.01...1.00 × I
n
0.01
Time multiplier CUBPTOC 0.05...15.00 0.01
Operating curve type
1)
CUBPTOC Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Operate delay time CUBPTOC 50...200000 ms 10
Alarm delay time CUBPTOC 50...200000 ms 10
1) For further reference, refer to the Operating characteristics table
Table 59. Three-phase current unbalance protection for shunt capacitor banks (HCUBPTOC)
Characteristic
Value
Operation accuracy Depending on the frequency of the measured current: f
n
±2 Hz
1.5% of the set value or 0.002 × I
n
Start time
1)2)
Typically 26 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode 1% of the theoretical value or ±20 ms
Operate time accuracy in IDMT mode 5% of the theoretical value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2,3,4,5,..
1) Fundamental frequency current = 1.0 × I
n
, current before fault = 0.0 × I
n
, fault current = 2.0 ×
Start value
, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 60. Three-phase current unbalance protection for shunt capacitor banks (HCUBPTOC) main settings
Parameter
Function Value (Range) Step
Start value HCUBPTOC 0.01...1.00 × I
n
0.01
Alarm start value HCUBPTOC 0.01...1.00 × I
n
0.01
Time multiplier HCUBPTOC 0.05...15.00 0.01
Operating curve type
1)
HCUBPTOC Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Operate delay time HCUBPTOC 40...200000 ms 10
Alarm delay time HCUBPTOC 40...200000 ms 10
1) For further reference, refer to the Operating characteristics table
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1