31
F-18
Sequence not found after 10 trials.
The load is varying too quicly.
Re-start the Autoset procedure under
more stable conditions.
F-19
Unknown sequence.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-20
Sequence error : closest value is 1:1:1:1:1.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-21
Sequence error : closest value is 1:2:2:2:2.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-22
Sequence error : closest value is 1:2:4:4:4.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-23
Sequence error : closest value is 1:2:4:8:8.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-24
Sequence error : closest value is 1:1:2:2:2.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-25
Sequence error : closest value is 1:1:2:4:4.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
F-26
Sequence error : closest value is 1:1:2:4:8.
The controller could not find a known
sequence.
Check connections,
capacitors and fuses
Message Description Recommended action

Other manuals for ABB RVC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RVC and is the answer not in the manual?

ABB RVC Specifications

General IconGeneral
Frequency50/60 Hz
Temperature Range-25°C to +55°C
MountingPanel Mounting
ManufacturerABB
Protection ClassIP20
CommunicationModbus RTU
Number of Steps4, 6, 8, 12