Section 3 Technical Data and Performance Power Supply and Cooling Requirements
3BSE015969-600 A 149
AI893 125 mA - - 0.6 2.0 55/40C (131/104F)
(2)
AI895 130 mA - 370 mA
including
sensor
current
4.75 16 55/40C (131/104F)
(2)
AO801 70 mA - 200 mA
including
load
current
3.8 13 55/40C (131/104F)
(2)
AO810 70 mA - 200 mA
including
load
current
3.0 10 55/40C (131/104F)
(2)
AO810V2
(3)
70 mA - 245 mA
including
load
current
2.3 7.8 55/40C (131/104F)
(2)
AO815 125 mA - 165 mA
including
load
current
3.5 12 55/40C (131/104F)
(2)
AO820 100 mA 260 mA - 6.0 20 55/40C (131/104F)
(2)
AO845/
AO845A
125 mA - 165 mA
including
load
current
3.5 12 55/40C (131/104F)
(2)
Table 32. I/O Station Power and Cooling (Typical) Values (Continued)
Device
5 Volts
ModuleBus
24 Volts
ModuleBus
24 Volts
External
Power
Dissipation
(Watts)
Cooling
Load
(1)
(BTU/H
Typical)
Maximum Ambient
Temperature