Power Supply and Cooling Requirements Section 3 Technical Data and Performance
150 3BSE015969-600 A
AO890 150 mA - 300 mA
including
load
current
3.5 12 55/40C (131/104F)
(2)
AO895 130 mA - 330 mA
including
load
current
4.25 14.5 55/40C (131/104F)
(2)
CI801 - - 140 mA 5.4 W
(3)
19 55/40C
(131/104F)
(10)
CI810 - - 110 mA 2.6 8.9 55C/(131F)
CI820/
CI820V1
- - 250 mA
(4)
6.0 20 55C/(131F)
CI840/
CI840A
- - 190 mA
(4)
7.7 26 55/40C
(131/104F)
(10)
DI801 70 mA - - 2.2 7.5 55/40C (131/104F)
(2)
DI802 50 mA - - 2.8 9.6 55/40C (131/104F)
(2)
DI803 50 mA - - 2.8 9.6 55/40C (131/104F)
(2)
DI810 50 mA - - 1.8 6.1 55/40C (131/104F)
(2)
DI811 50 mA - - 2.7 9.2 55/40C (131/104F)
(2)
DI814 50 mA - - 1.8 6.1 55/40C (131/104F)
(2)
DI818 70mA - 25mA 3.1 55/40°C (131/104°F)
(2)
DI820 50 mA - - 2.8 9.6 55/40C (131/104F)
(2)
DI821 50 mA - - 2.8 9.6 55/40C (131/104F)
(2)
Table 32. I/O Station Power and Cooling (Typical) Values (Continued)
Device
5 Volts
ModuleBus
24 Volts
ModuleBus
24 Volts
External
Power
Dissipation
(Watts)
Cooling
Load
(1)
(BTU/H
Typical)
Maximum Ambient
Temperature

Table of Contents

Related product manuals