EasyManuals Logo

ABB S800 User Manual

ABB S800
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #162 background imageLoading...
Page #162 background image
Intrinsic Safety Parameters Section 3 Technical Data and Performance
162 3BSE015969-600 A
Table 38. AI895 Analog Input Module Intrinsic Safety Parameters
Terminals
Safety
Description
Maximum External Parameters
Groups CENELEC USA C
0
(uF) L
0
(mH) L/R (uH/O)
1-10, 2-11
3-12, 4-13
5-14, 6-15
7-16, 8-17
U
0
= 27 V IIC AB 0.087 4.1 55
I
0
= 93 mA IIB CE 0.702 16.4 222
P
0
= 630 mW IIA DFG 2.23 32.8 443
Table 39. AO890/AO895 Analog Output Module Intrinsic Safety Parameters
Terminals
Safety
description
Maximum external parameters
Groups CENELEC USA C
0
(uF) L
0
(mH) L/R (uH/O)
Powered
output
terminals
U
0
= 27 V IIC AB 0.097 4.1 58
I
0
= 93 mA IIB CE 0.74 16.5 230
P
0
= 620 mW IIA DFG 2.51 33 470
Table 40. DI890 Digital Input Module Intrinsic Safety Parameters
Terminals
Safety
description
Maximum external parameters
Groups CENELEC USA C
0
(uF) L
0
(mH) L/R (uH/O)
Input
terminals
U
0
= 11V IIC AB 1.97 80 595
I
0
= 21 mA IIB CE 13.8 320 2382
P
0
= 0.058
mW
IIA DFG 60 640 4765

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB S800 and is the answer not in the manual?

ABB S800 Specifications

General IconGeneral
ManufacturerABB
MountingDIN Rail
Power Supply24 V DC
Protection ClassIP20
CertificationsCE, UL, ATEX
Number of ChannelsVaries depending on module type
ModelS800
Communication ProtocolsProfibus DP, Modbus
RedundancyYes (depending on module and communication interface)

Related product manuals