Section 3 Technical Data and Performance Intrinsic Safety Parameters
3BSE015969-600 A 163
Table 41. DO890 Digital Input Module Intrinsic Safety Parameters
Terminals
Safety
description
Maximum external parameters
Groups CENELEC USA C
0
(uF) L
0
(mH) L/R (uH/O)
Powered
output
terminals
U
0
= 26 V IIC AB 0.099 4.1 58
I
0
= 93 mA IIB CE 0.77 16.4 234
P
0
= 605 mW IIA DFG 2.6 32.8 469