Section 2 Product Description I/O Modules
3BSE015969-600 A 49
AI830/
AI830A
Analog Input 1*8 ch, Pt100 (-80...80
o
C, -200...250
o
C,
-200...850
o
C), Ni100 (-60...180
o
C),
Ni120 (-80...260
o
C), Cu10 (-100...260
o
C)
Resistor (0...400 ), 14 bit.
Pt100 according to IEC751 ITPS-68, IEC ITP-90, US Ind
Std, US lab Std, JIS C 1604:1981 and JIS C 1604:1997
Ni100 according to DIN 43760
Ni120 according to MIL-T-24388C
Cu10 according to TCR 0.00427
Rated insulation voltage 50 V.
AI835/
AI835A
Analog Input 1*8 ch Thermocouple (TC),
type B (0...1820
o
C), type C (0...2300
o
C),
type E (-270...1000
o
C), type J (-210...1200
o
C),
type K (-270...1372
o
C), type N (-270...1300
o
C),
type R (-50...1768
o
C), type S (-50...1768
o
C),
type T (-270...400
o
C), linear -30...75 mV, 14 bit.
Rated insulation voltage 50 V.
AI843 Analog Input 1*8 ch Thermocouple (TC),
-30 mV to 75 mV linear, or TC types B, C, E, J, K, L, N, R,
S, T, and U, 16 bit.
Rated insulation voltage 50 V
Advanced on-board diagnostics.
For single and redundant applications.
AI845 Analog Input 1*8 channels. 0...20 mA, 4...20 mA, 0...5 V,
1...5 V, 12 bit, 0,1%. HART interface.
Rated insulation voltage 50 V.
Advanced on-board diagnostics.
For single and redundant applications.
Table 7. S800 Analog Modules (Continued)
Module
Type
Type
(1)
Description

Table of Contents