ABB | SACE Emax 2
Ekip Dip
2 - Operator interface
33 | © 2023 ABB | 1SDH001000R0002 - ECN000297030
LED
The LEDs are useful on Ekip Dip in order to distinguish and identify various types of information on the
protection trip unit, the circuit-breaker and state of the line currents.
The LEDs combined with the protections provide various information, through different combinations of
lighting and blinking.
NOTE:
all the combinations related to protection LED signals are described in chapter
Self-
diagnosis and signalling
, on page
40.
Protections: Thresholds and
timing
The thresholds of all the protections can be modified with various dip-switches, as specified on the
serigraph of the interface.
The values of the protections make reference to the current In, a nominal value defined by the Rating Plug.
The times and the curves of the protections can be modified with various dip-switches, as specified on
the serigraph of the interface.
IMPORTANT:
Changes to the thresholds and times must be made in the absence of protection alarms.
Modifications carried out in alarm conditions are accepted by the trip unit when resting
condition is restored (absence of protection alarms).
Settings
Two further settings are available:
Neutral allows activation and adjustment of the protections on the neutral pole.
Frequency allows the selection of the installation frequency.
iTest pushbutton
The iTest pushbutton is useful for three operations:
Perform tests (circuit-breaker opening test and LED test).
Reset the signal of the tripped protection. This operation can be performed when the circuit-breaker
is both open and closed and with currents present, by pressing the push-button for about 1 second
(the signal disappears when the push-button is released).
With the trip unit off, check the information relating to the switch-off or tripping event.
NOTE:
with the trip unit off, pressing of the iTest button switches on (for approximately 4
seconds):
the power-on LED, if the trip unit is off due to an energy drop (primary current less than the
minimum level of operation, removal of auxiliary power supply with circuit-breaker open,
etc…).
the protection tripped LED if the trip unit is off due to a protection trip.
Test connector
The test connector allows the connection of Ekip TT and Ekip T&P modules (purchased separately), in
order to perform the following operations:
The release can be provided with temporary power supply for state verification and conduction of
trip tests and LED tests (option available with all front interface modules).
Analysis, supervision and setting of additional parameters through external communication test
units (Ekip T&P).