Ekip Dip
2 - Operator interface
32 | © 2023 ABB | 1SDH001000R0002 - ECN000297030
2 - Operator interface
Introduction
The operator interface of the Ekip Dip protection release allows you to:
Set the parameters relating to the available protections.
View the status of the trip unit and alarms.
Connect to the frontal connector to communicate and perform the opening test.
Components of the interface
The Ekip Dip operator interface appears as follows:
Figure 76
The following table provides a description of the components of the interface:
Position Type Description
A
LED
L Protection LED (alarm and trip)
B L Protection LED (pre-alarm)
C S Protection LED (alarm and trip)
D I Protection LED (trip)
E G Protection LED (alarm and trip)
F Power-on LED (trip unit powered and on)
G
Protections:
thresholds
L Protection dip-switch (threshold I1)
H S Protection dip-switch (threshold I2)
I I Protection dip-switch (threshold I3)
L G Protection dip-switch (threshold I4)
M
Protections: times
L Protection dip-switch (time t1)
N S Protection dip-switch (time t2 and type of curve)
O G Protection dip-switch (time t4 and type of curve)
P Settings Neutral and frequency dip-switch
Q
Test
Test pushbutton
R Test connector
IMPORTANT: the figure above refers to an Ekip Dip, LSIG version. In the case of Ekip Dip
LI or LSI versions, LEDs and dip-switches related only to the protections present are
available.