ABB | SACE Emax 2
Electronic accessories | 3 - Ekip Synchrocheck module
177 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the module:
Parameter Values Default Description
Primary Voltage
100 V, 115 V, 120 V, 190 V,
208 V, 220 V, 230 V, 240 V,
277 V, 347 V, 380 V, 400 V,
415 V, 440 V, 480 V, 500 V,
550 V, 600 V, 660 V, 690 V,
910 V, 950 V, 1000 V, 1150 V
100 V
Primary voltage of the
isolation transformer.
Secondary
Voltage
100 V, 110 V, 115 V, 120 V 100 V
Secondary voltage of the
isolation transformer.
Concatenated
Ref
V12, V23, V31 V12
Input phase-to-phase voltage
to the module.
NO Contact No, Yes Yes
Status of the contact:
• No = Normally closed.
• Yes = Normally open.
The following table illustrates the path from the display to view information on the module and
synchronism status:
Information
Protection unit
Circuit-breaker
Modules
…
Ekip Synchrocheck
…
Power Controller
The information that can be displayed is as follows:
• The serial number and the software version.
• The overall synchronism status (“Ok” or “Not OK”).
• The correspondence between the voltage, frequency, and phase values (“Ok” or “Not OK”).