ABB SACE SACE PR010/T RH0025002 L2551 13/20
20
13. Proceed as described in point 7 onwards.
5.2.2 Test report downloading procedure
1. Switch on the SACE PR010/T test unit.
2. Using the cable supplied, connect the unit to one of the PC's serial ports
3. Run the "SD-TU Interface" program.
4. On the PR010/T menu select Get report
5. On the main menu of the SACE PR010/T unit, select
’2.Report Download’,
the following message will be displayed:
’Test report download’
’ENTER to start’
6. Press ENTER on the SACE PR010/T unit to display the following message:
’Waiting for report download’.
Before one minute elapses, press the Get report key in the window "get report from PR010/
T" displayed on the PC.
7. The SACE PR010/T unit will now display the message:
’Download in progress’
accompanied by a progressive status bar indicating the download time remaining. The
maximum transmission duration is about one minute.
8. If the file is not successfully downloaded, the SACE PR010/T unit will display the message:
9. ’END report download’
10. ’Press ESC to restart’
11. while the PC will automatically open the Report window displaying what has been
received.
12. Press ESC on the SACE PR010/T unit to return to the main menu.
13. If the file is not successfully downloaded, the SACE PR010/T unit will display the message:
’Download aborted’
’Press ESC to return’
14. The PC will display the message "Timeout error: cannot contact PR010/T"
15. Press ESC and resume as described in point 4 onwards.
16. In the event of problems not described in this section, refer to the "Error messages and
troubleshooting table".