ABB SACE SACE PR010/T RH0025002 L2551 15/20
20
The specifications of the external power supply supplied are as follows:
The specifications of the rechargeable batteries supplied are as follows:
The operating autonomy of the batteries during testing depends on the type of release tested, the
type of tests performed, the different release versions and the operations performed by the user.
When testing, for example, a PR112/P unit the batteries operate for about 2 hours under test
conditions and 6 hours in stand-by mode.
The battery recharge time is about four hours with unit switched off.
The batteries recharge automatically when the SACE PR010/T test unit is connected to the
external power supply.
The rechargeable batteries are supplied discharged. The batteries must therefore be charged
before using the PR010/T test unit for the first time.
The test unit may also be connected to the external power supply.
6.3 Inputs/Outputs
The SACE PR010/T test unit uses a set of signals to perform its various testing, programming and
reading functions. The main characteristics of these signals are as follows:
Vin = 100...240 Vac (47...63 Hz)
Vout = 12 Vdc ±5%
Max output current = 2.7A
Size AA
Ty pe N iM H
Voltage 1.2V
Capacity 1300 mA/h
Output voltage range: - 5 … +12 Vdc
Maximum output current: 1A constant
Input voltage range: 0 … +15 Vdc
Minimum input impedance: 1 Mohm