1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 51
This voltage determines the change of the trip threshold I20, with different
behaviour according to selective mode:
The value is expressed both as an absolute value (Volt) and as a relative
value (Un), settable in a range: 0.2 Un .. 1 Un with 0.01 Un step
The parameter is shown with a Lin curve and helps to calculate the trip
threshold I21:
The threshold varies gradually (see
above)
The value is expressed both as an absolute value (Volt) and as a relative
value (Un), settable in a range: 0.2 Un .. 1 Un with 0.01 Un step
Threshold I20 calculation constant.
The value is expressed as a percentage value of the threshold I20,
which is settable in a range: 0.1 I20 .. 1 I20 with 0.01 step
This is the trip time of the protection.
The value is expressed in seconds, which are settable in a range:
0.05 s .. 30 s, with 0.01 s step
Constraints, limitations, and additional functions
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access the block functions, see page70.