What to do if trip command fails on ABB SACE Tmax XT7 Circuit breakers?
K
Keith MillsAug 19, 2025
If the ABB Circuit breaker fails to open or current is still present after a trip command, you should comply with the procedure proposed in the next chapter 'Faults, causes and remedies'.
T
Teresa BennettAug 21, 2025
What to do if I see a numerical alarm on my ABB Circuit breakers?
T
Tina MichaelAug 21, 2025
If you encounter a numerical alarm (e.g., 30002) on your ABB Circuit breakers, it indicates an internal error. In this case, contact ABB for assistance.
A
Arthur AlvarezAug 23, 2025
Why am I getting a configuration error on my ABB SACE Tmax XT7?
A
Alexandra PetersAug 23, 2025
If there's an error related to the protection parameter configuration in your ABB Circuit breakers, ensure that the threshold I4 and time t4 are compatible with the minimum values required for self-supply.
S
Sarah HarrisAug 26, 2025
How to fix 'Ethernet disconnected' error on ABB SACE Tmax XT7?
J
Jonathan JohnsonAug 26, 2025
If the ABB Circuit breakers display an 'Ethernet disconnected' error, it means there is no external cable connected to one or more Ekip Com modules with an Ethernet connection. Check the cable connections.
J
Jennifer AcostaAug 28, 2025
What does 'Measuring Error' mean on ABB Circuit breakers?
K
kbakerAug 28, 2025
If the ABB Circuit breakers show a 'Measuring Error', which means there is a measurement module parameter reading error, you should contact ABB.
A
Ashley HayesAug 30, 2025
How to fix 'Invalid Date' error on ABB SACE Tmax XT7?
R
Rodney HamiltonAug 31, 2025
If your ABB Circuit breakers display an 'Invalid Date', set the correct date and time in Settings-System-Date and Settings-System-Time.
Z
zsmithSep 1, 2025
How to troubleshoot 'Local bus' error on ABB Circuit breakers?
J
Jeffery RussellSep 1, 2025
If you get a 'Local bus' error on your ABB Circuit breakers, check the following:
* Connection and powering of modules in the terminal box or external.
* Ensure that the modules connected are compatible with Ekip Touch.
This error occurs when the unit is on with auxiliary supply, the Local Bus parameter is enabled, but the connection to modules is not present, incorrect, or communication is lost for more than five seconds.
E
Emily EdwardsSep 4, 2025
What does 'Ekip Link Bus' fault mean on ABB Circuit breakers?
J
Jeffrey OliverSep 4, 2025
If your ABB Circuit breakers indicate 'Ekip Link Bus' fault, check for loss of connection with one or more actors (modules) connected to the Link Bus.
E
Erin JohnsonSep 6, 2025
What does 'SNTP error' mean on ABB Circuit breakers?
R
Richard SchwartzSep 6, 2025
If your ABB Circuit breakers display 'SNTP error', it indicates a synchronization problem of SNTP synchronization reference module with Ekip Com modules.
L
Lisa RodriguezSep 8, 2025
What does 'Ekip Sign 3T connection' alarm mean on ABB SACE Tmax XT7?
C
churleySep 9, 2025
If your ABB Circuit breakers display 'Ekip Sign 3T connection' alarm, it indicates the connection of one or more analog inputs to the Ekip Signalling 3T module.