ABB | SACE Tmax XT
Ekip Touch - Settings | 1 - Main settings129 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Test Bus
The parameter allows parameter editing via the service connector to be enabled/disabled, thereby limiting
the possibility of configuring all the options on the display (in the Local mode) or via modules Ekip Com (in
the Remote mode).
Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
unauthorized persons to be increased.
NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
Ekip Touch is supplied with the parameter set to: On.
System
The System menu provides various options:
Parameter Description Default
Date Setting the current date
Time Setting the current time
Language Setting the language in display menus English
PIN PIN setting (page 41) 00001
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset
and if necessary replace the battery inside Ekip Touch (page 19).
View
The View menu provides various options:
Parameter Description Default
TFT orientation
Enables the orientation of the Alarms List, Measuring Instruments and
Main Measurements pages to be set. The options are: Horizontal, Vertical
clockwise, Vertical counter-clockwise
Horizontal
Customer page
Allows you to activate a supplementary information page, which can
be accessed by pressing the iTEST button twice from any page with a
diagnosis bar. The information on the new page can be configured via Ekip
Connect (page 132)
Off
Ammeter Phase
Allows the current to be displayed in the Measuring instruments page to be
set from among the following options: Imax, I1, I2, I3, Ne (only in the 4P or
3P + N configuration)
Imax
Voltmeter Phase
Allows the voltage to be displayed in the Measuring instruments page to be
set from among the following options: Vmax, V12, V23, V31
Vmax
Maintenance
The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 112).
Ekip Touch is supplied with the parameter set to: On.