Protections | 14 - Motor protections71 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
14 - Motor protections
List
The Motor Protection package, available by default and only for Ekip M Touch, comprises protections:
Name Type of protection Page
R JAM Motor block (post startup) 72
R STALL Motor block (always activated) 72
UC Under-current 73
U Phase loss 73
PTC Maximum temperature 74
The Motor protections conform to standard IEC 60947-4-1 and relative annex 2.
Trip class and parameters
The trip class mentioned in standard IEC 60947-4-1 is available in Trip units with Motor Class parameter
(page 130).
Its value establishes:
the trip time of L protection (Time t1)
the start-up time (Motor start-up), calculated from the moment that at least one phase exceeds the fixed
threshold of 0.25 x I1, during which some protections are inhibited
the thermal memory L reset time after a TRIP (tmem res)
Motor Class t1 (s) Motor start-up (s) tmem res (min)
5E 12 3 5
10E 22 5 10
20E 45 10 20
30E 72 20 33
Figure 31
NOTE: temporary switch-off during Motor Statup-up is valid and activated for protections G,
R Jam and U if enabled; if the protections are disabled they remain off before and after
Motor start-up
Thresholds
Unlike the other current protections, the R Stall, R Jam and UC thresholds are not related to In, but to
threshold I1 (L protection), given as Ir in the respective configuration menus;
Example
Rating plug = 400 A, Threshold I1 = 0.8 In (--> 320 A); Threshold Ij = 2.5 Ir (--> 2.5 x 320 A = 800 A)