ABB | SACE Tmax XT
Ekip Touch - Default | 1 - Ekip TOUCH default parameters135 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Default
1 - Ekip TOUCH default parameters
Foreword
Given the number of parameters available with Ekip Touch, each chapter describing their characteristics also
includes their default value settings.
The configurations of the main parameters are given below.
Protections
All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
exception of the protections listed below:
Protection Configuration
L
I1= 1 In; t1= 144 s; curve= t= k/I
2
; prealarm: 90% I1
I I3= 4 In; startup= OFF
Harmonic distortion On
Rc
(1)
Idn= 3 A; Tdn= 0,06 s
(1) protection available and active if model Rc Rating Plus is present
Parameters
Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
following configurations:
Parameters Configuration
Frequency 50 Hz (IEC) / 60 Hz (UL)
Configuration 3P (3P circuit-breaker) / 4P (4P circuit-breaker)
Neutral Off (3P circuit-breaker) / 50% (4P circuit-breaker)
Rated voltage 400 V
Power flow Top Bottom
Phase Sequence 1-2-3
Local bus Off
Mode Local
Language English
Bluetooth Low Energy Off
Password 00001
Home page Histograms
Led Alive Disabled
View Horizontal
Maintenance On
Test Bus On
Modbus RTU par Address: 247; baudrate: 19.2 Kbit/s
Profibus Address: 125
DeviceNet
TM
MAC ID: 63; baudrate: 125 Kbit/s
Modbus TCP/IP Static IP: 0.0.0.0