ABB | SACE Tmax XT
130 | © 2020 ABB | 1SDH001821A1002 - ECN000135670 Ekip Touch - Settings | 1 - Main settings
MLRIU
The MLRIU parameters are available with Ekip M Touch for the Motor Protections functions (page 71).
NOTE: to ensure correct operation, check where applicable: presence and status of the
outgoing connections, those towards the Trip unit of Ekip CI and the relative output
contact (O61)
Parameters
Parameter Description Default
Open Mode
Allows the TRIP mode to be set (page 42):
Heavy: in the event of a TRIP, it is controlled by the Trip coil of the CB
Normal: contact O61 of the Ekip CI module is opened in the event of a
TRIP
NOTES:
the TRIP for protections G or I always involves the Trip coil
command, regardless of the Open Mode configuration
in the Normal mode, if the Trip unit detects the presence of a fault
even after the open command sent to O61, a command is also sent to
the Trip coil of the CB
Standard
Autoreclosure
Enabled
When Open Mode= Normal, allows re-closing of contact O61 to be activated
after a TRIP due to protection L (On)
Off
Motor Class
Allows the trip class of the motor to be selected from among: 5E, 10E, 20 E,
30E (page 71)
Contactor Delay
Defines the time waited, after the open command of contact O61, before
the fault is considered to be still present and action is taken by sending a
command to the Trip coil of the CB. The value is given in seconds and can
be set within the range: 0.1 s to 1 s, in 0.1 s steps
0,1
Autoreclosure
Time
Defines the time waited after the open command of contact O61, before
this latter is closed. The value is given in seconds and can be set within the
range: 1 s to 1000 s, in 1 s steps
60