Code Factory Value and function
setting
S3 0 Field contact type
0 = NO contact, with return function
1 = NC contact, with return function
2 = raising edge only
3 = falling edge only
4 = raising and the falling edge
5 = pulse counter, counts by contact closing
6 = pulse counter, counts by contact opening
7 = pulse counter, counts by contact opening and closing
S4 0 Channel related sequence
0 = visual indication in accordance with selected sequence
1 = visual indication in accordance with selected sequence,
but with audible alarm also on return to normal
2 = field contact following visual indication without audible alarm
S5 0 Channel reflash A
0 = not connected
1 = connected to reflash group 1
2 = connected to reflash group 2
S6 0 Channel reflash B
0 = not connected
1 = connected to reflash group 1
2 = connected to reflash group 2
S7 0 Interlocking signal 1, type specification
0 = interlocking output
1 = interlocking input, reflash A blocked
2 = interlocking input, entire channel, return as acknowledged alarm
3 = interlocking input, entire channel, return as new alarm
S8 0 Interlocking signal 1, grouping
0 = not connected
1...8 = connected to interlocking line 1...8
S9 0 Interlocking signal 2, type specification
0 = interlocking output
1 = interlocking input, reflash A blocked
2 = interlocking input, entire channel, return as acknowledged alarm
3 = interlocking input, entire channel, return as new alarm
S10 0 Interlocking signal 2, grouping
0 = not connected
1...8 = connected to interlocking line 1...8
S11 0 Pumping supervision
0 = not connected
1...99 = allowed events per minute
V5 0 Pulse counter
0...29999 = start value
I1 - Sate of alarm channel
0 = not active
1 = active