38
Code Factory Value and function
setting
V201 2 Setting of the data transfer rate
0 = 9600 bits/s, synch in
1 = 9600 bits/s, synch out
2 = 9600 bits/s
3 = 4800 bits/s
4 = 2400 bits/s
5 = 1200 bits/s
6 = 300 bits/s
I1 - State of interlocking line 1
0 = not active state
1 = active state
I2 - State of interlocking line 2
I3 - State of interlocking line 3
I4 - State of interlocking line 4
I5 - State of interlocking line 5
I6 - State of interlocking line 6
I7 - State of interlocking line 7
I8 - State of interlocking line 8
O1 - Sate of output relay 1
0 = not active state
1 = active state
O2 - Sate of output relay 2
C 0 Status information of module
0 = when read normal state, when written resets the status register
1 = CPU reset has occurred
2 = overflow of the event register has occurred
3 = 1 + 2
F SACO Type designation of module
16D2B
T - Time setting
0.000...59.999 = time in seconds and milliseconds
L - Event sequence register
Time, channel and event code
B - Repeated read out of event register
Time, channel and event code
A - Active alarms
Channel number and event code
Channel related parameters (alarm channels 1...16)
S1 0.02 Channel input delay
0.005...160.0 = reset delay
0.005 s steps
S2 0.02 Channel reset delay
0.005...160.0 = reset delay
0.005 s steps

Table of Contents