10
PAINOS
PAINOS
Output relay matrix switchgroups SGR1, SGR2 and SGR3
SGR1 The switches of switchgroup SGR1 are used to select the protective stages to be
brought to the starting signal output SS1 and the tripping signal output TS2.
SGR2 The switches of switchgroup SGR2 are used for configurating the tripping signals of the
different protective stages. There are two outputs, SS2 and SS3, to which the signals can be
linked.
SGR3 The switches of switchgroup SGR3 are used for configurating the starting and tripping
signals to the starting or auxiliary tripping output TS1. Note! If the circuit breaker failure protec-
tion has been selected in with switch SGF1/4, it will also utilize the TS1 output.
Switch Function Factory Checksum
setting value
SGR1/1 When SGR1/1 = 1, the starting signal of stage I> is linked to SS1 1 1
SGR1/2 When SGR1/2 = 1, the tripping signal of stage I> is linked to TS2 1 2
SGR1/3 When SGR1/3 = 1, the starting signal of stage I>> is linked to SS1 0 4
SGR1/4 When SGR1/4 = 1, the tripping signal of stage I>> is linked to TS2 1 8
SGR1/5 When SGR1/5 = 1, the starting signal of stage I
o
> is linked to SS1 0 16
SGR1/6 When SGR1/6 = 1, the tripping signal of stage I
o
> is linked to TS2 1 32
SGR1/7 When SGR1/7 = 1, the staring signal of stage I
o
>> is linked to SS1 0 64
SGR1/8 When SGR1/8 = 1, the tripping signal of stage I
o
>> is linked to TS2 1 128
Checksum for factory setting of SGR1 171
SGR2/1 When SGR2/1 = 1, the tripping signal from stage I> is linked to SS2 1 1
SGR2/2 When SGR2/2 = 1, the tripping signal from stage I> is linked to SS3 0 2
SGR2/3 When SGR2/3 = 1, the tripping signal from stage I>> is linked to SS2 1 4
SGR2/4 When SGR2/4 = 1, the tripping signal from stage I>> is linked to SS3 0 8
SGR2/5 When SGR2/5 = 1, the tripping signal from stage I
o
> is linked to SS2 0 16
SGR2/6 When SGR2/6 = 1, the tripping signal from stage I
o
> is linked to SS3 1 32
SGR2/7 When SGR2/7 = 1, the tripping signal from stage I
o
>> is linked to SS2 0 64
SGR2/8 When SGR2/8 = 1, the tripping signal from stage I
o
>> is linked to SS3 1 128
Checksum for factory setting of SGR2 165