Ex relevant specifications
CI/TZIDC/110/120-EN TZIDC, TZIDC-110, TZIDC-120 35
7 Ex relevant specifications
IMPORTANT (NOTE)
The values indicated here are taken from the respective certificates. Always observe the
specifications and supplements in the explosion protection certificates.
7.1 TZIDC
: s
7.1.1 ATEX Ex i
Designation:
II 2 G Ex ia IIC T6 resp. T4 Gb
II 2 G Ex ib IIC T6 resp. T4 Gb
II 2 D Ex ia IIIC T51°C resp. 81°C Db
Type Examination Test Certificate: TÜV 04 ATEX 2702 X
Type: Intrinsically safe equipment
Device class: II 2G
Standards:
Device class:
Standards:
EN 60079-0:2009
EN 60079-11:2012
II 2D
EN 60079-0:2009
EN 61241-11:2006
II 2 G
Temperature class
Ta
Ambient temperature range
T4 -40 ... 85 °C
T5 -40 ... 50 °C
T6
1)
-40 ... 40 °C
1) When using the "digital feedback" plug-in module in temperature class T6, the maximum permissible ambient
temperature range is -40 ... 35 °C.
II 2 D
Housing surface temperature
Ta
Ambient temperature range (II 2 D)
T81 °C -40 ... 70 °C
T61 °C -40 ... 50 °C
T51 °C -40 ... 40 °C

Table of Contents