24
4. Panel design and equipment
Door interlocking
The panels are equipped with the following
interlocks:
The apparatus (circuit-breaker or contactor)
can not be racked-in if the apparatus
compartment door is open. This interlock is
not available for emergency manual
operation with motorized withdrawable
apparatus.
The apparatus compartment door cannot be
opened if the apparatus (circuit-breaker or
contactor) is in service or in an undefined
position.
The earthing switch cannot be operated if
the cable compartment door is open.
The cable compartment door cannot be
opened if the earthing switch is open.
Note:
When the interlocking for circuit-breaker is used
then it is necessary to use the OFF push button
on the door to provide emergency switching OFF.
Interlocks between panels
The busbar earthing switch can only be
closed when all the withdrawable parts in the
relative busbar section are in the test /
disconnected position (electromechanical
interlock).
When the busbar earthing switch is closed,
the withdrawable parts in the earthed busbar
section cannot be moved from the test /
disconnected position to the service position
(electromechanical interlock).
Locking devices
The shutters can be secured independently
of each other with padlocks when the
withdrawable circuit-breaker part has been
removed.
Access to the operating-shaft of the earthing
switch can be restricted with a padlock.
Access to the circuit-breaker racking slot can
be restricted with a padlock.
Access to the circuit-breaker compartment
and the cable compartment can be restricted
with a padlock.
WARNING
The locking magnet is not installed in the
case of a motor operator; busbar earthing
switches or the withdrawable parts are
electrically locked. The manual emergency
switch is not locked!
The apparatus compartment door interlock
is not available for motor operated
withdrawable apparatus as a mechanical
device (Figure 22). Manual operation of a
motorized withdrawable circuit-breaker
part should be performed in emergency
case only!
WARNING
The door’s handle which is an integral part
of doors has to be push to its final close
position – see Figure 18 of closed and not
closed position of door’s handle.
In case the door’s handle is not in its final
close position the doors are not closed yet.
In this case the interlock function cannot be
ensured.
Figure 18: A) Closed position of door’s handle; B) Not
closed position of door’s handle