22 ABB Power Distribution
Store the panels upright.
Do not stack panels.
Panels with basic packaging:
Open the packaging, at least partially.
Panels without packaging:
Loosely cover with protective sheeting.
Ensure that there is sufficient air circulation.
Check regularly for any condensation until the
start of installation.
2. Panels with seaworthy or similar packaging with
internal protective sheeting:
Store the transport units:
protected from the weather,
in a dry place,
safe from damage.
Check the packaging for damage.
Check the drying agent (see also section 4.2):
on arrival of the consignment,
later at regular intervals.
When the maximum storage period, starting
from the date of packaging, has been
exceeded:
the protective function of the packaging
can no longer be guaranteed,
take suitable action if intermediate storage
is to continue.
Note:
Do not walk on the roof of the panels (rupture
points in pressure relief devices)!
Figure 4/1: Handling by crane
1.5 Lifting lug
1.18 Marking on the centre of gravity
ø 35
1.5
1.18
60°