ABB Power Distribution 29
Figure 5/2a: Switchgear with pressure relief via absorber into the
switchroom,
panel width: 650/800/1000 mm
Figure 5/2b: Switchgear without pressure relief duct,
panel width: 650/800/1000 mm
Figure 5/2c: Switchgear with pressure relief to the outside,
panel width: 800/1000 mm
Figure 5/2d: Switchgear with pressure relief duct and diverter,
pressure relif into the switchroom,
panel width: 800/1000 mm
Figure 5/2e: Switchgear with pressure relief to the outside,
Switchgear with toroidal-core current transformers,
panel width: 1000 mm
Figure 5/2: Sections for figure 5/1
See figure 5/1 for legend
FT = panel width
1)
Minimum dimensions
2)
When minimum dimension
1)
are changing the corresponding dimension
2)
must be adjusted accordingly.
1)
180
1)1)
460
1075
2100
180
295
100
FT + 200
H + 200
3000
600
1150
FT + 7001350
530
H = 2200
H = 2595
9
14
10
13
8
2685
2050 650
920
100
16
Section E - E
12
11
6
17
ZS1: > 25kA
200
(100)
(80)
2)
2)
180
1)
1)
1)
2100
180
195
50
FT + 200
H + 200
3000
600
360
1050
FT + 7001300
1075
(80)
530
H = 2200
H = 2595
9
14
10
13
12
11
8
6
17
2685
ZS1: > 25kA
2050 650
870
50
16
Section C - C
200
(100)
2)
2)
1)
1)
1)
180
50
FT + 200
H + 200
3000
600360
200
1050
FT + 7001300
(100)
1075
(80)
180 530
H = 2200
H = 2595
2650
9
14
10
13
12
11
8
6
7
195
ZS1: 25kA
Section A - A
2)
2)
1)
1)
1)
180
50
FT + 200
H + 200
3000
600360
200
1050
FT + 7001300
(100)
1075
(80)
180 530
H = 2200
H = 2595
9
14
10
13
12
11
8
6
15
195
Section B - B
2600
2100
2)
2)
(100)
1)
1)
1)
180
195
50
FT + 200
H + 200
3200
600360
1050
FT + 700
1300
1075
(80)
530
H = 2200
H = 2595
9
14
10
13
12
11
8
17
6
2685
ZS1: > 25kA
2950
18
2100
180
Section D - D
200
2)
2)